Studi Analisa Sistem Penangkal Petir pada Area Kantor Pariwisata Kota Pariaman

Analysis of the Lightning Protection System at the Pariaman City Tourism Office Area

Authors

  • Bismal Iqbal Program Studi Teknik Elektro, Fakultas Teknik, Universitas Ekasakti, Jl. Veteran No. 26B – Kota Padang – Indonesia
  • Yani Ridal Program Studi Teknik Elektro, Fakultas Teknik, Universitas Ekasakti, Jl. Veteran No. 26B – Kota Padang – Indonesia
  • Budiman Program Studi Teknik Elektro, Fakultas Teknik, Universitas Ekasakti, Jl. Veteran No. 26B – Kota Padang – Indonesia

DOI:

https://doi.org/10.56338/jks.v9i7.11656

Keywords:

Gedung Pariwisata Kota Pariaman, Penangkal Petir, Rolling Sphere, Sistem Pembumian, Tahanan Tanah, Grounding System, Lightning Protection, Pariaman City Tourism Building, Rolling Sphere, Soil Resistance.

Abstract

Gedung Pariwisata Kota Pariaman merupakan bangunan bertingkat dengan ketinggian 16 meter yang berfungsi sebagai pusat operasional pelayanan pariwisata dan terletak di wilayah pesisir pantai sehingga memiliki risiko tinggi terhadap sambaran petir. Pada gedung tersebut telah dipasang sistem penangkal petir konvensional tipe sangkar Faraday (Faraday cage) dengan tinggi tiang 4 meter. Penelitian ini bertujuan menganalisis tingkat kebutuhan serta efektivitas sistem penangkal petir yang terpasang berdasarkan standar PUIPP dan indeks kriteria bahaya. Hasil analisis menunjukkan gedung termasuk kategori bangunan dengan tingkat bahaya tinggi dengan nilai R lebih dari 14. Data hari guruh tahun 2024 menunjukkan sebanyak 207 hari guruh dengan arus puncak petir sebesar 81,6977 kA. Perhitungan tegangan sentuh, tegangan langkah, sudut perlindungan, dan radius proteksi dilakukan menggunakan metode rolling sphere. Hasil menunjukkan cakupan proteksi optimal dengan luas area perlindungan sebesar 603,18 m² yang dihasilkan oleh tiga terminal udara. Nilai tahanan pentanahan diperoleh sebesar 1,75 ? dengan tahanan jenis tanah 4,887 ?m, sehingga sistem penangkal petir dinyatakan efektif melindungi gedung.

ABSTRACT

The Pariaman City Tourism Building is a 16-meter multi-story building that serves as the operational center for tourism services and is located in a coastal area, giving it a high risk of lightning strikes. A conventional Faraday cage lightning protection system with a 4-meter mast has been installed on the building. This study aims to analyze the level of need and the effectiveness of the installed lightning protection system based on the PUIPP standard and the danger criteria index. The analysis shows that the building falls into the high-risk category with an R value greater than 14. The 2024 thunderstorm-day data shows 207 thunderstorm days with a peak lightning current of 81.6977 kA. The calculation of touch voltage, step voltage, protection angle, and protection radius was carried out using the rolling sphere method. The results show optimal protection coverage with a protected area of 603.18 m² produced by three air terminals. The grounding resistance value was 1.75 ? with a soil resistivity of 4.887 ?m, so the lightning protection system is declared effective in protecting the building.

References

Andriansyah, R. (2024). Evaluasi Perbaikan Tahanan Pentanahan Penangkal Petir pada Pabrik Cocoa Teaching Industry Universitas Gadjah Mada.
Bandri, S. (2012). Analisa Sistem Penangkal Petir pada Balai Kota Pariaman. Jurnal Teknik Elektro Institut Teknologi Padang.
Collins, H., dkk. (2021). Research Design and Case Study Methods in Engineering.
Harsono, B. B. S. D. A., Surya, A. S., Mangunkusumo, K. G. H., & Purnomoadi, A. P. (2021). Karakteristik Petir Indonesia dan Penggunaannya dalam Evaluasi Unjuk Kerja Saluran Udara 150 kV saat Terjadi Sambaran Petir. Jurnal Technopreneur (JTech), 9(1), 46–53.
Ihsan, A. F., & Widihastuti, I. (2025). Analisa Perlindungan Sistem Penangkal Petir terhadap Gangguan Petir pada Gedung-Gedung Area Rumah Sakit Islam Sultan Agung Semarang. Jurnal Ilmu Pendidikan dan Pembelajaran, 7(2), 121–132.
Kantonno, E. R., Setiadji, J. S., & Hosea, E. (2023). Evaluasi Perencanaan Sistem Kelistrikan Rumah Sakit “X” Berdasarkan PUIL 2011 dan Aplikasi Ecodial. Jurnal Teknik Elektro, 16(2), 41–46.
Pangestu, A. (2020). Pengaruh Sambaran Petir terhadap Kinerja Rele Jarak. Universitas Muhammadiyah Sumatera Utara, Medan.
Putra, I. Z., Anas, A. A. P., Hasnira, H., & Nakul, F. (2024). Evaluasi Sistem Proteksi Petir Eksternal Konvensional pada Gedung PT Infineon Batam-3. Journal of Applied Electrical Engineering, 8(1), 63–69.
Sahgal, R. (2024). Metode Rolling Sphere dalam Penentuan Zona Proteksi Sistem Penangkal Petir.
Viona, F., Anshar, C. N., & Ridal, Y. (2025). Analisa Sistem Penangkal Petir pada Gedung Polda Sumatera Barat, 6(1).
William Suharto, D., Nisworo, S., & Trihasto, A. (2021). Perlindungan Sambaran Petir Bangunan Publik (Studi Kasus Pasar Induk Kabupaten Wonosobo). Prosiding Seminar Nasional Riset Teknologi Terapan, 2–5.

Published

2026-08-13